Close
(0) Shopping cart
You have no items in your shopping cart.
Shopping Categories
    Filters
    Preferences
    Search
    RSS

    Tag: ac contactors

    How to Repair AC Contactors?

    Contact system maintenance

    • Check whether the position of the movable and static contact points is aligned, whether the three-phase is closed at the same time; Adjust the contact spring in case of any problem.
    • Check the wear degree of contact points, the wearing depth shall not be more than 1mm. In case of contact burning or welding falling, please replace timely; Slight burning will not affect the application. The sand paper can not be used to clean the contact, a shaping file is suitable.
    • The resistance shall not be less than 10MΩ when measuring the interphase insulation resistance;
    • Check whether the auxiliary contact acts flexibly, the contact travel should comply with the specified value. Check whether the contact is loosening, maintain or replace timely in case of any problem.