I have a few other questions:
1. I am installing the VFD in an IP55 enclosure and I need to add 250V indicator lights on the enclosure door.
Is it ok to connect one leg of the light to U terminal and the other to neutral to indicate the motor is running?
2. In my country we use PME, that means the neutral is bonded to earth.
Is it ok to connect the earth that has been bonded to neutral to the earth terminal of the VFD unit?
From:
jorel
|
Date:
05/02/2023
Was this review helpful?
Yes
No
(0/0)
1. If you want to install a running indicator light on the door panel when the VFD is running, you can use the VFD relay output signal to control it.
The terminal is TA/TB/TC (TA-TB: NO contact), the corresponding parameter is P4.12, set P4.12=0 (VFD running).
2. In this case, you can directly connect your local ground wire to the ground wire of the VFD (terminal marked E), or not ground.