The single-phase current monitoring relay equipped with LED lights, quickly understands the working status of the equipment. It can be used through overdrive/flow monitor mode, which is equipped to handle a wide input voltage range, accepting AC/DC 12-240V inputs. The current monitoring relay has fast operation speed, high accuracy, good maneuverability, and a current range of 2-20A, which have led to its widespread use in power systems, such as rail switches, heating cables, and consumption of one-phase motors, indicating current flow.
Feature
- Through center design, no need to disconnect the current circuit, throughcenter installation is convenient to use.
- Cover/Under current monitoring mode can be set by knob.
- With AC and DC universal testing specifications optional.
- An isolation current transformer is adopted, and external current transformers can be connected to expand the monitoring current range.
- 2 C/O output.
- Universal supply AC/DC 24-240 V.
- Relay status is indicated by LED.
- 1-MODULE, DIN rail mounting.
Model and Connotation
Technical Parameters
Model |
ATO-GRI8-06A |
ATO-GRI8-06B |
Function |
AC measurement |
AC/DC measurement |
Supply Terminals |
A1-A2 |
Rated Supply Voltage |
AC/DC 24-240V |
Rated Supply Frequency |
50/60Hz,0 |
Burden |
Max 25VA |
Supply Voltage Tolerance |
-15%;+10% |
Current Range |
2A-20A |
Current Frequency |
AC 50Hz |
AC 50Hz , DC |
Setting Method |
Potentiometer |
Supply Indication |
Green LED |
Setting Accuracy |
10% |
Hysteresis |
5% |
Output |
2×SPDT |
Current Rating |
8A/AC1 |
Switching Voltage |
250VAC/24VDc |
Min. breaking Capacity DC |
500mW |
Output Indication |
Red LED |
Mechanical Life |
1×107 |
Electrical Life (AC1) |
1×105 |
Operating Temperature |
-20°℃ ~+55°℃ |
Storage Temperature |
-35℃~+75°℃ |
Mounting/ DlN Rail |
Din rail EN/ IEC 60715 |
Protection Degree |
IP20 |
Operating Position |
Any |
Overvoltage Cathegory |
III. |
Pollution Degree |
2 |
Max. cable Size (mm2) |
1×2.5mm or 2×1.5mm 0.4·Nm |
Dimensions |
90mm×36mm×64mm |
Weight |
90g |
Standards |
EN 60255-1 |
Functions Diagram
Tr: Power-up delay.
Tt: Tripping delay.
Wiring Diagram
Monitored Current ≤ 20A
Monitored Current > 20A, Through CT Transformation
Panel Diagram
Dimensions (mm)
Tips: The working principle of a single-phase current monitoring relay
The working principle of a 1-phase current monitoring relay and the principles of electromagnetics and electromagnetic sensing. When an electric current occurs in this line, a constant electromagnetic wave is generated, producing an electric current. This sensitive electric current influences the magnetic field in the sphere and then influences the state of the contact point. Through the parameters of the rational design, precise control of the current control device can be realized. For example, by changing the number of circles, material, length, etc.